The EXTRA-HEAVY GRADE STEEL CALCIUM SULPHATE CORE FULL ENCAPSULATED(EDGE FOLDED TYPE)  RAISED ACCESS FLOOR will provide a stable platform suitable for the general office & equipment room environments. The panel comprises of a high strength calcium sulphate core laminated on its bottom and top with galvanised steel. The top face is then covered with the required laminate finish. The panel sides are finished with connection by folding of top and bottom galvanised steel plate. The panels will be corner locked into place providing equipotential bonding or they can be gravity held with or without stringers. The cross-head or flat-head pedestal head will provide support for the panel under the flange and picture frame. The pedestal head will also capture the access floor panel providing positive location and additional safety after the corner lock screws are removed. The raised access floor system will be capable of withstanding various duty static/dynamic loads experienced in the general office and equipment environments.   Any requirement of technical details/test report/certificate/new products and etc, Please ask details through company sales by email:  susan@upinfloor.com

Products Details

Product Details

System Performance Criteria

Applications

Key performance characteristics: -Panel type C30E, size 600x600x30m, panel weight: 20kgs/pc, Calcium sulphate panel with density>1800kgs/cbm. -Panel type C30, size 600x600x30m, panel weight: 20kgs/pc, Calcium sulphate panel with density>1400kgs/cbm. -Panel type C34, size 600x600x34m, panel weight: 23kgs/pc, Calcium sulphate panel with density>1800kgs/cbm. -Panel type C38, size 600x600x38m, panel weight: 26kgs/pc, Calcium sulphate panel with density>1800kgs/cbm. -Top finish High pressure laminate, conductive PVC, vinyl, plywood tile, composite wood panel, porcelain tile, terrazzo and etc. -Bottom galvanized steel plate -Edge with conductive PVC -Conductive adhesive
Panel type conc.load uniform load ultimate load safety factor rolling load impact load
C30E-FS1500 6700N 42600N 20100N 3 10 times 5600N 10000 times 4500N 670N
Panel type conc.load uniform load ultimate load safety factor rolling load impact load
C30-FS1500 6700N 42600N 20100N 3 10 times 5600N 10000 times 4500N 670N
Panel type conc.load uniform load ultimate load safety factor rolling load impact load
C34-FS2000 8900N 49800N 26700N 3 10 times 6700N 10000 times 5600N 780N
Panel type conc.load uniform load ultimate load safety factor rolling load impact load
C38-FS2500 11100N 58300N 33300N 3 10 times 8900N 10000 times 6700N 780N
Create prefect data center or general office environment by UPIN’s raised access floor system. Widely used in in airport, bank, office buildings, school, laboratories, hospitals, factories, clean rooms and etc.

Benefits

-Economical -Excellent load bearing and high level of stability -Quite -easy-to-install -provide a variety of open area percentage by perforated panel and grate panel. -Power and Data Management Flexibility -Freedom with design and layout options -Environmentally friendly: low VOCs, recycle content